Heating is a very nice service - especially in winter.
Some Commands Examples
Set mode
*4*102*5## set zone 5 in anti-freeze mode
*4*110*5## set zone 5 in manual mode
*4*303*5## set zone 5 OFF
Set temperature
*#4*#5*#14*0250*3## set zone 5 to 22.5°C
Some Request Examples
*#4*2*0## get current temp of zone 2
returns *#4*2*0*0225## = temperature in zone 2 is 22.5°C
Some Monitor Message Examples
In these examples, the zone is always zone 5
*#4*5*0*0161## current temperature: 16.1 °C
*#4*5*12*0070*3## real set point (set point + offset): 7.0 °C
*4*102*5## is in anti-freeze mode
*#4*5*14*0215*3## set point: 21.5 °C
Manual offset of zone 5
*#4*5*13*00## manual offset: 0
*#4*5*13*01## manual offset: +1°C
*#4*5*13*02## manual offset: +2°C
*#4*5*13*03## manual offset: +3°C
*#4*5*13*11## manual offset: -1°C
*#4*5*13*12## manual offset: -2°C
*#4*5*13*13## manual offset: -3°C
*4*102*#5## is in anti-freeze mode
WHAT Table
WHAT
|
Description
|
0
|
Conditioning Mode
|
1
|
Heating Mode
|
102
|
Anti Freeze
|
202
|
Thermal Protection
|
302
|
Protection (generic)
|
103
|
OFF – Heating Mode
|
203
|
OFF – Conditioning Mode
|
303
|
OFF (Generic)
|
110
|
Manual-adjustment Mode – Heating
|
210
|
Manual-adjustment Mode – Conditioning
|
310
|
Manual-adjustment Mode (Generic)
|
111
|
Programming Mode – Heating
|
211
|
Programming Mode - Conditioning
|
311
|
Programming Mode (generic)
|
115
|
Holiday daily plan – Heating Mode
|
215
|
Holiday daily plan – Conditioning Mode
|
315
|
Holiday daily plan
|
13xxx
|
Vacation scenario for xxx days – Heating mode (Xxx=0…999)
|
23xxx
|
Vacation scenario for xxx days – Conditioning mode (xxx=0….999)
|
33xxx
|
Vacation scenario for xxx days (xxx=0….999)
|
3000
|
Vacation scenario disabled
|
11xx
|
Heating program x (x=1…3)
|
21xx
|
Conditioning program x (x=1…3)
|
31xx
|
Last activated program
|
3100
|
Scenario xx (xx=1…16)
|
12xx
|
Scenario xx (xx=1...16)
|
22xx
|
Last activated scenario
|
32xx
|
Holiday scenario for xxx days – Heating mode (Xxx=0…999)
|
3200
|
Holiday scenario for xxx days – Conditioning mode (xxx=0….999)
|
20
|
Remote control disabled
|
21
|
Remote control enabled
|
22
|
At least one probe OFF
|
23
|
At least one probe in Anti Freeze
|
24
|
At least one probe in Manual
|
30
|
Failure discovered
|
31
|
Central Unit battery KO
|
40
|
Release of sensor local adjustment
|
DIMENSION Table
DIMENSION
|
Description
|
ReadOnly/ReadWrite
|
0
|
Measures Temperature
|
R
|
11
|
Fan coil Speed
|
R
|
12
|
Complete probe status
|
R
|
13
|
Local set offset
|
R
|
14
|
Set Point temperature
|
R/W
|
19
|
Valves status
|
R
|
20
|
Actuator Status
|
R
|
22
|
Split Control
|
R/W
|
30
|
End date Holiday Scenario
|
R/W
|