Difference between revisions of "WHO=1 - Lighting"

From piMyHome Project
Jump to navigation Jump to search
Line 146: Line 146:
 
|#1*p*s
 
|#1*p*s
 
|Set dimmer p% up with s seconds (0..254) dimming time
 
|Set dimmer p% up with s seconds (0..254) dimming time
 +
|- style="vertical-align:top;"
 
|#2*h*m*s
 
|#2*h*m*s
 
|Turn ON light for a certain time<br>Values for hours, minutes, seconds are integer
 
|Turn ON light for a certain time<br>Values for hours, minutes, seconds are integer

Revision as of 16:50, 2 November 2015

Standard Command

Syntax: *WHO*WHAT*WHERE##
Examples:

*1*1*23##        Turn on light 23  
*1*0*23##        Turn off light 23  
*1*7*45##        Set dimmer 45 to 70%  
*1*18*37##       Turn on light 37 for 0.5 sec (useful for door opener etc.)  
*1*29*23##       Let light 23 blink for 5 sec (useful as a 'silent' alarm) 
*1*30*45##       Set dimmer 45 up to next level (+10%)  

WHAT Reference Standard Command (WHO=1)

Value Description
0 OFF
0#s Turn OFF dimmer with s seconds (0..254) dimming time
to arrive at OFF
A value of "0" seconds will use last used dimming time
1 ON
If dimmer: ON with last percentage
1#x Turn ON dimmer with s seconds (0..254) dimming time
to arrive at last percentage of dimmer
A value of "0" seconds will use last used dimming time
2 Set dimmer to 20%
3 Set dimmer to 30%
4 Set dimmer to 40%
5 Set dimmer to 50%
6 Set dimmer to 60%
7 Set dimmer to 70%
8 Set dimmer to 80%
9 Set dimmer to 90%
10 Set dimmer to 100%
11 ON for 1 min
12 ON for 2 min
13 ON for 3 min
14 ON for 4 min
15 ON for 5 min
16 ON for 15 min
17 ON for 30 sec
18 ON for 0.5 sec (useful as a push button)
20 Blinking with a frequency of 0.5 sec
21 Blinking with a frequency of 1 sec
22 Blinking with a frequency of 1.5 sec
23 Blinking with a frequency of 2 sec
24 Blinking with a frequency of 2.5 sec
25 Blinking with a frequency of 3 sec
26 Blinking with a frequency of 3.5 sec
27 Blinking with a frequency of 4 sec
28 Blinking with a frequency of 4.5 sec
29 Blinking with a frequency of 5 sec
30 Dimmer up to next 10% step
30#p#s Dimmer p% up with s seconds (0..254) dimming time
If dimmer was off before, turns on to p%
Dimmer arrives max. at 100%
A value of "0" seconds will use last used dimming time
31 Dimmer down to previous 10% step
31#p#s Dimmer p% down with s seconds (0..254) dimming time
Lowest percentage the dimmer arrives is 1%
A value of "0" seconds will use last used dimming time
1000# Internal Command translation, visible in monitor session only.



Parameter Commands

Syntax: *#WHO*WHERE*#PARAMETER*VALUE1[*VALUE2...]##
Examples:

*#1*43*#2*1*35*18##        Turn on light 43 for 1h:35m:18s
*#1*44#4#03*#2*0*0*13##    Turn on light 44 of interface 03 for 13s

*#1*43#4#02*#9*1##         Set max working hours to one hour


Parameter Command Reference (WHO=1)

Parameter & Values Description
#1*p*s Set dimmer p% up with s seconds (0..254) dimming time
#2*h*m*s Turn ON light for a certain time
Values for hours, minutes, seconds are integer
#9*h Set max working time in hours
Values for hours are integer

Status Request

Syntax: *#WHO*WHERE##


Sending a Status Request to the gateway results in a Standard Message reply.

*#1*23##      Request status of light 23   
*#1*45##      Request status of light 45 
*#1*37##      Request status of light 37  

That 45 is a dimmer, we might realize when we get another reply than 0 or 1.


WHO=0 - Scenarios WHO Table WHO=2 - Automation