WHO=1 - Lighting
Standard Message *WHO*WHAT*WHERE##
Examples:
*1*1*23## Turn on light 23 *1*0*23## Turn off light 23 *1*7*45## Set dimmer 45 to 70% *1*18*37## Turn on light 37 for 0.5 sec (useful for door opener etc.) *1*29*23## Let light 23 blink for 5 sec (useful as a 'silent' alarm) *1*30*45## Set dimmer 45 up to next level (+10%)
Status Request *#WHO*WHERE##
Sending a Status Request to the gateway results in a Standard Message reply.
*#1*23## Request status of light 23 *#1*45## Request status of light 45 *#1*37## Request status of light 37
That 45 is a dimmer, we might realize when we get another reply than 0 or 1.
WHAT Reference WHO=1
Value | Description |
---|---|
0 | OFF |
0#s | Turn OFF dimmer with s seconds (0..254) dimming time to arrive at OFF A value of "0" seconds will use last used dimming time |
1 | ON If dimmer: ON with last percentage |
1#x | Turn ON dimmer with s seconds (0..254) dimming time to arrive at last percentage of dimmer A value of "0" seconds will use last used dimming time |
2 | Set dimmer to 20% |
3 | Set dimmer to 30% |
4 | Set dimmer to 40% |
5 | Set dimmer to 50% |
6 | Set dimmer to 60% |
7 | Set dimmer to 70% |
8 | Set dimmer to 80% |
9 | Set dimmer to 90% |
10 | Set dimmer to 100% |
11 | ON for 1 min |
12 | ON for 2 min |
13 | ON for 3 min |
14 | ON for 4 min |
15 | ON for 5 min |
16 | ON for 15 min |
17 | ON for 30 sec |
18 | ON for 0.5 sec (useful as a push button) |
20 | Blinking with a frequency of 0.5 sec |
21 | Blinking with a frequency of 1 sec |
22 | Blinking with a frequency of 1.5 sec |
23 | Blinking with a frequency of 2 sec |
24 | Blinking with a frequency of 2.5 sec |
25 | Blinking with a frequency of 3 sec |
26 | Blinking with a frequency of 3.5 sec |
27 | Blinking with a frequency of 4 sec |
28 | Blinking with a frequency of 4.5 sec |
29 | Blinking with a frequency of 5 sec |
30 | Dimmer up to next 10% step |
30#p#s | Dimmer p% up with s seconds (0..254) dimming time If dimmer was off before, turns on to p% Dimmer arrives max. at 100% A value of "0" seconds will use last used dimming time |
31 | Dimmer down to previous 10% step |
31#p#s | Dimmer p% down with s seconds (0..254) dimming time Lowest percentage the dimmer arrives 1% A value of "0" seconds will use last used dimming time |
1000# | Internal Command translation, visible in monitor session only. For example, dimmer 43 up for 15% in 5 seconds: *1*30#15#5*43## will be translated internally to #1*43#4#02*1*155*5 where 155 is the new 'percentage' 55%, before it was 140 = 40%) |
Dimension | Info |
---|---|
speed | 0..255 (0=now, 255=slowest) |
step | one step = 10% of dimmer |
WHERE | Address |
---|---|
0 | General |
1..9 | Environment 1 to 9 |
11..99 | Light point 1.1 to 9.9 |
0110..0915 | Light point 1.10 to 9.15 |
#1..#9 | Group 1 to 9 |
WHO=0 - Scenarios | WHO Table | WHO=2 - Automation |