WHO=1 - Lighting
Contents
Standard Messages
Standard Command
Syntax: *WHO*WHAT*WHERE##
Examples:
*1*1*23## Turn on light 23 *1*0*23## Turn off light 23 *1*7*45## Set dimmer 45 to 70% *1*18*37## Turn on light 37 for 0.5 sec (useful as push button for door opener etc.) *1*21*23## Let light 23 blink with a frequency of 1 sec (useful as a 'silent' alarm) *1*30*45## Set dimmer 45 up to next 10% step
Standard Request
Syntax: *#WHO*WHERE##
Sending a Status Request to the gateway results in a Standard Message reply.
*#1*23## Request status of light 23 *#1*45## Request status of light 45 *#1*37## Request status of light 37
That 45 is a dimmer, we might realize when we get another reply than 0 or 1.
Standard Command Reference WHAT (WHO=1)
Value | Description |
---|---|
0 | OFF |
0#s | Turn OFF dimmer with s seconds (0..254) dimming time to arrive at OFF A value of "0" seconds will use last used dimming time |
1 | ON If dimmer: ON with last percentage |
1#s | Turn ON dimmer with s seconds (0..254) dimming time to arrive at last percentage of dimmer A value of "0" seconds will use last used dimming time |
2 | Set dimmer to 20% |
3 | Set dimmer to 30% |
4 | Set dimmer to 40% |
5 | Set dimmer to 50% |
6 | Set dimmer to 60% |
7 | Set dimmer to 70% |
8 | Set dimmer to 80% |
9 | Set dimmer to 90% |
10 | Set dimmer to 100% |
11 | ON for 1 min |
12 | ON for 2 min |
13 | ON for 3 min |
14 | ON for 4 min |
15 | ON for 5 min |
16 | ON for 15 min |
17 | ON for 30 sec |
18 | ON for 0.5 sec |
20 | Blinking with a frequency of 0.5 sec |
21 | Blinking with a frequency of 1 sec |
22 | Blinking with a frequency of 1.5 sec |
23 | Blinking with a frequency of 2 sec |
24 | Blinking with a frequency of 2.5 sec |
25 | Blinking with a frequency of 3 sec |
26 | Blinking with a frequency of 3.5 sec |
27 | Blinking with a frequency of 4 sec |
28 | Blinking with a frequency of 4.5 sec |
29 | Blinking with a frequency of 5 sec |
30 | Dimmer up to next 10% step |
30#p#s | Dimmer p% up with s seconds (0..254) dimming time If dimmer was off before, turns on to p% Dimmer arrives max. at 100% A value of "0" seconds will use last used dimming time |
31 | Dimmer down to previous 10% step |
31#p#s | Dimmer p% down with s seconds (0..254) dimming time Lowest percentage the dimmer arrives is 1% A value of "0" seconds will use last used dimming time |
1000# | Internal Command translation, visible in monitor session only. |
Parameter Messages
Parameter Command
Syntax: *#WHO*WHERE*#PARAMETER*VALUE1[*VALUE2...]##
Examples:
*#1*43*#2*1*35*18## Turn on light 43 for 1h:35m:18s *#1*44#4#03*#2*0*0*13## Turn on light 44 of interface 03 for 13s *#1*23*#9*1## Set max working hours of light 23 to one hour
Parameter Request
Syntax: *#WHO*WHERE*#PARAMETER##
Examples:
*#1*43*#2## Get remaining countdown time
Parameter Reference (WHO=1)
Parameter | Description |
---|---|
#1 | Returns dimmer status *#1*WHERE*1*PERCENTAGE*DIMMINGTIME## |
#1*p*s | Set dimmer p% up with s seconds (0..254) dimming time Didn't work for me |
#2 | Returns the remaining countdown time until light switches of *#1*WHERE*2*HOURS*MINUTES*SECONDS## |
#2*h*m*s | Turn ON light for a certain amount of time (countdown timer) Values for hours, minutes, seconds are integer |
#3 | Returns some "Required Only ON Light ???" Didn't work for me |
#8 | Returns the total amount of hours, the light was powered on *#1*WHERE*8*HOURS## |
#9 | Returns Max amount of hours working time lamp |
#9*h | Set max. 'working time' in hours Values for hours are integer Didn't work for me |